Product overview
3.1 Properties
Properties
The module has the following technical properties:
• Connects the ET 200MP distributed I/O system
– with PROFINET IO
• 24 VDC supply voltage (SELV/PELV)
• PROFINET IO connection via selectable BusAdapters
– BA 2×RJ45 for RJ45 bus connector
– BA LC/RJ45 as media converter for glass fiber-optic cable ⇔ standard RJ45 connector
– BA 2xLC for glass fiber-optic cable
– BA SCRJ/RJ45 as media converter for POF/PCF fiber-optic cable ⇔ standard RJ45
– BA 2xSCRJ for POF/PCF fiber-optic cable
– BA SCRJ/FC as media converter for POF/PCF fiber-optic cable ⇔ direct connection of the
– BA LC/FC as media converter for glass fiber-optic cable ⇔ direct connection of the bus
– BA 2×FC for direct connection of the bus cable
– BA 2xM12 for bus cable with M12 plug
• Supported topologies
– Tree topology
• Pulling and plugging I/O modules on the active backplane bus (multi hot swapping)
• You can find additional information in the Active backplane bus
(https://support.industry.siemens.com/cs/ww/en/view/109769815) Equipment Manual.
The module supports the following functions (Page 22).
Maximum configuration I/O data
• 1440 bytes I/O data per station
Maximum configuration Active backplane bus
• The integrated power supply of the interface module feeds 16 W into the backplane bus.
Up to 12 I/O modules can be supplied in this way when operating with an active
backplane bus. The exact number of operable modules is determined by the power budget
(see relevant section in the system manual S7-1500, ET 200MP Automation system