Interrupts and diagnostic, error, and system alarms
6.1 Status and error displays
Meaning of the LEDs RUN/ ERROR/ MAINT
Table 6- 1
Meaning of the LEDs RUN/ ERROR/ MAINT
LEDs
RUN
ERROR
MAINT
Off
Off
Flashes
Flashes
Flashes
On
On
Flashes
Off
Not
relevant
relevant
On
Not
relevant
relevant
Flashes
Not
Not
relevant
relevant
Flashes
Flashes
Flashes
Flashes
Flashes
Flashes
48
Supply voltage not present or too low at
interface module
Off
Test of the LEDs during startup: The three
LEDs light up simultaneously for approx.
3.0 s in red, then for approximately 0.25 s
in green.
The LEDs light up simultaneously for several
seconds. Hardware or firmware defective.
On
Error information is determined and stored
retentively in flash memory.
Interface module is deactivated.
Off
Interface module is not configured.
ET 200MP is starting up.
ET 200MP is being reset to factory settings.
Not
ET 200MP is currently exchanging data with
the IO controller.
Not
Group error and group error channels
The set configuration does not correspond
to the actual configuration of the ET 200MP.
Invalid configuration states
Parameter assignment error in the I/O mod-
ule
Maintenance
On
Hardware or firmware defective. (The LEDs
P1 and P2 of the PROFINET interface are not
flashing.)
"Node flash test" is being performed. (The
LEDs P1 and P2 of the PROFINET interface
are also flashing.)
Meaning
Interface module IM 155-5 MF HF (6ES7155-5MU00-0CN0)
Remedy
Check the supply voltage or turn it on at the
interface module.
---
Wait until the trace data are saved. If all
LEDs are flashing, you can read out the
data.
Activate the interface module with the con-
figuration software or the user program.
Configure the interface module with the
configuration software.
---
Evaluate the diagnostics and correct the
error.
Check the configuration of the ET 200MP to
see whether a module is missing or defec-
tive, or whether a non-configured module is
inserted.
See section Invalid configuration states of
the ET 200MP on PROFINET IO (Page 58)
Evaluate the display of the module status in
STEP 7 and correct the error in the corre-
sponding I/O module.
See section Maintenance events (Page 52)
Run a firmware update. If the error persists,
contact Service & Support.
Replace the interface module.
---