SP Reset Correct
[25SPRST]
Barometric Standard
[26BARSTD]
Barometric Correct
[27BARCOR]
Calibrate High Point
[28CAL HI]
Calibrate Low Point
[29CAL LO]
ST 800 Pressure Transmitter User's Manual
63
Resets SP Zero Correct
###. ###
One point field offset
Calibration Method for AP
transmitters only
######. ##
######. ##
Executing this selection resets
Static Pressure Zero to the
factory value of 0.
Enter an atmospheric pressure
value corresponding to a
barometric standard.
If the difference between the
measured atmospheric pressure
and the user- entered
barometric standard pressure is
> 1 psi (27.680672 inH2O
[4°C]) the
calibration will not be performed.
Range: 330-490 inH2O [4°C]
Default: 406.782 inH2O [4°C]
Adjusts the pressure measured
by the AP transmitter with the
user entered barometric
standard.
Cal high point value in inH2O
[4°C]
Range: LRV to URV
Default: URV
Cal low point value in inH2O
[4°C]
Range: LRV to URV
Default: LRV
Press  to
enter menu
selection
Press  to
initiate action
Press  to
enter menu
selection
 Menu to
select
number.
 to enter and
shift to the
next digit to
the right
Press  to
enter menu
selection
Press  to
initiate action
Press  to
enter menu
selection
 Menu to
select
number.
 to enter and
shift to the
next digit
to the right
Press  to
enter menu
selection
 Menu to
select
number.
 to enter and
shift to the
next digit
to the right