SP Reset Correct
[25SPRST]
Barometric Standard
[26BARSTD]
Barometric Correct
[27BARCOR]
Calibrate High Point
[28CAL HI]
Calibrate Low Point
[29CAL LO]
ST 800 Pressure Transmitter User's Manual
63
Resets SP Zero Correct
###. ###
One point field offset
Calibration Method for AP
transmitters only
######. ##
######. ##
Executing this selection resets
Static Pressure Zero to the
factory value of 0.
Enter an atmospheric pressure
value corresponding to a
barometric standard.
If the difference between the
measured atmospheric pressure
and the user- entered
barometric standard pressure is
> 1 psi (27.680672 inH2O
[4°C]) the
calibration will not be performed.
Range: 330-490 inH2O [4°C]
Default: 406.782 inH2O [4°C]
Adjusts the pressure measured
by the AP transmitter with the
user entered barometric
standard.
Cal high point value in inH2O
[4°C]
Range: LRV to URV
Default: URV
Cal low point value in inH2O
[4°C]
Range: LRV to URV
Default: LRV
Press to
enter menu
selection
Press to
initiate action
Press to
enter menu
selection
Menu to
select
number.
to enter and
shift to the
next digit to
the right
Press to
enter menu
selection
Press to
initiate action
Press to
enter menu
selection
Menu to
select
number.
to enter and
shift to the
next digit
to the right
Press to
enter menu
selection
Menu to
select
number.
to enter and
shift to the
next digit
to the right
Revision 15