NOTES:
* "Cal Set B" item in menu is available only if sensor supports Dual calibration
** "Cal Set C" item in menu will be available only if sensor supports Triple calibration.
<Return> Return to the Level 1 menu
<Return>
Tag ID
Parameters
Damping (sec)
NAMUR
Selection
Filter
Performance
Transfer
Function
(Available only
for DP
transmitters)
Flow Cutoff
(Available only
when Transfer
Function is
Square Root)
36
Cal Set B*
Cal Set C**
Best Fit
Table 13 – Transmitter Setup Menus
##. #
Disabled
Enabled
Fast SOR
Std SOR
Linear
Square
Root
Single
Breakpt
Dual Slope
Zero flow
ST 800 Pressure Transmitter User's Manual
calibration set from
drop-down menu.
Enter Tag ID name up to 8
characters long.
= any
Alphanumeric value
Selection applies digital
filtering to suppress noise
effects on the PV. The limits
for this value are 0.0 to 32.0
seconds.
Disabling sets the loop output
and burnout levels to the
Honeywell levels
Enabling sets the loop output
and burnout levels to
the NAMUR levels
Fast Speed of Response
Standard Speed of Response
The loop output of the
transmitter is a linear
representation of the
differential pressure.
The loop output of the
transmitter represents
%Flow as defined by the
DP Square Root flow
equation.
Allows the user to specify a
single breakpoint as the low
flow cutoff point.
Uses a dual slope formula to
determine the low flow cutoff
point.
Sets loop output to 0
%Flow when the differential
pressure is below the low flow
cutoff point.
Press
or to select
calibration type.
to initiate
Press to enter
menu selection
and to select
Alphanumeric
to enter and shift to
next character to the
right.
Press to enter
menu selection Press
and to select
number. Press to
enter
and shift to next digit.
Press to enter
menu selection. Press
and to select
from list. Press to
enter.
Press to enter
menu selection. Press
and to select
from list. Press to
enter.
Press to enter
menu selection. Press
and to select
from list. Press to
enter.
Revision 15