6.1 Introduction

Accessories are available factory-installed and/or shipped loose. Obtain the most current list of accessories from the generator
set specification sheet or by contacting an authorized Kohler dealer.
Have accessories installed by your local authorized Kohler dealer or authorized representative. Follow the installation
instructions provided with each kit.
Use separate conduit for AC and DC leads to reduce the possibility of electrical interference. Use shielded cable for all analog
inputs. Verify that the leads and conduit do not interfere with the operation of the generator set or obstruct the service areas.
Refer to the wiring diagrams in the Diagrams and Drawings section for more information regarding generator set electrical
connections.
Verify that the accessory installation complies with the National Electrical Code (NEC) and all applicable local and state codes.
The following sections list some common accessories and their functions. Follow the installation instructions provided with the
kit.
DANGER
WARNING

6.2 Battery Heaters

The battery heater kit includes a heating battery wrap to help increase the battery temperature in cold climates and a thermostat
for controlled heating. The heater requires a 120 VAC, 15 amp. electrical outlet within reach of the power cord for each battery
heater wrap.
Note:
Battery heaters are compatible with all Kohler-supplied lead-acid batteries.
manufacturer's instructions for any restrictions regarding the use of battery heaters.
Battery heater wrap
Figure 30
Typical Battery heater
1
Battery heaters are not recommended for OPTIMA batteries, which are supplied for some applications. OPTIMA BATTERIES is a registered trademark of Johnson Controls, Inc.
TP-7203
4/23
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until it cools.
Power cord
Section 6. Accessories
1
For other battery types, check the battery
Retaining strap shown in vertical position
Retaining strap shown in horizontal position
TT-1740
49