Generator set terminal block.
Check the decal on the generator
set for terminal block connections.
Note:
See the Communication Cable Specifications section for
maximum cable lengths.
* RXT transfer switch with standard or combined
interface/load management board. Do not use a load shed
kit with a combined interface board.
Figure 17
Accessory Module Connections with 12-14 AWG Power Leads (one cable run with three modules shown)
32
12 AWG or 14 AWG leads
for PWR and COM.
Leave one end of each cable shield
disconnected at the last device.
Connect one end of each cable shield to
GROUND at the generator set.
Communication cable Belden #9402, #1075, or equivalent
20 AWG shielded, twisted-pair cable (one pair).
Connect shields
together as shown.
TP-7203
4/23