Reset Calibration
Pressing the select button when "Reset Calibration? Yes" is displayed will discard the changes and reset the calibration to the
original settings. See Figure 44.
Generator - - >
Metering
Three-phase
Volts L1- L2:
Volts L2- L3:
Volts L3- L1:
Frequency:
Note:
Pressing select when Reset Calibration: Yes is displayed will discard the changes and reset the calibration to the original settings.
Figure 44
Voltage Calibration
TP-7203
4/23
Calibrate
240 V
Calibrate
240 V
Calibrate
240 V
60.0 Hz
Single-phase
Volts:
240V
Frequency:
60.0 Hz
Reset
Calibration
<- - Return
Calibrate
To Calibrate Voltage:
1. Press Select when the voltage is
displayed. The voltage flashes.
2. Press the Up or Down arrow button
to change the setting.
3. Press the Select button to save the
setting.
4. Press the down arrow button to
move to the next menu.
Reset
Calibration? No
Reset
Calibration? Yes
TP-6811
63