16
|
Special requirements for R32 units

16.4.3 Natural ventilation

Installer and user reference guide
74
Note: Depending on configuration, the remote controller is operable in three
possible modes. Each mode offers different controller functionality. For detailed
information about setting the operation mode of the remote controller and its
function, please refer to the installer and user reference guide of the remote
controller.
Mode
Fully functional
Alarm only
Supervisor
Note: Incorrect use of remote controllers can result in occurrence of error codes,
non-operating system or system that is not compliant to applicable legislation.
Note: Some centralised controllers can also be used as supervisor remote
controller. For further details on installation, please refer to the installation manual
of the centralised controllers.
Example
A remote controller installed at a supervised location.
▪ In room: master remote controller in fully functional OR alarm only.
▪ In supervisor room: supervisor remote controller
a
b
c
a Outdoor unit
b SV unit
c Indoor unit
d Remote controller compatible with R32 safety system
e Remote controller in supervisor mode
f Supervisor room
Natural ventilation is a safety measure where ventilation is made to a place where
sufficient air is available to dilute the leaked refrigerant such as a large space.
Function
The controller is fully functional. All normal
functionality is available. This controller can be master
or slave.
The controller only acts as leak detection alarm (for a
single indoor unit). No functionality is available. The
remote controller should always be put in the same
room as the indoor unit. This controller can be master
or slave.
The controller only acts as leak detection alarm (for
the whole system, i.e. multiple indoor units and their
respective controllers). No other functionality is
available. The remote controller should be placed at a
supervised location. This remote controller can only
be the slave.
Note: In order to add a supervisor remote controller to
the system, a field setting must be set on remote
controller and outdoor unit. Indoor units and SV units
need to be assigned an address number.
c
d
d
e
f
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12