RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
Mounting the outdoor unit (see
WARNING
Fixing method of the outdoor unit MUST be in accordance with the instructions from
this manual. See
Connecting the refrigerant piping (see
4
piping" [
 102])
WARNING
Field piping MUST be in accordance with the instructions from this manual. See
"18 Piping
installation" [
CAUTION
Piping MUST be installed according to instructions given in
4
installation"  [
compliant with the latest version of ISO14903 can be used.
Low temperature solder alloys shall not be used for pipe connections.
CAUTION
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this unit to guarantee its lifetime. The drying material may
dissolve and damage the system.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
WARNING
During tests, NEVER pressurise the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
3
Specific installer safety instructions
|
"17.3 Mounting the outdoor
"17.3 Mounting the outdoor
"18.2 Connecting the refrigerant
4
 90].
  90]. Only mechanical joints (e.g. braze+flare connections) that are
4
unit" [
 88])
4
unit" [
 88].
"18  Piping
Installer and user reference guide
15