21
|
Configuration
Installer and user reference guide
154
[2‑49]
Height difference setting.
[2‑49]
0 (default)
1
Other changes/limitations to the circuit apply. For more information see
"18.1.8 Single and multi-outdoor-unit
[2‑54]
Indoor unit connection setting.
[2‑54]
0 (default)
1
[2‑60]
Supervisor remote controller setting. A power reset is required to save this setting.
For details about the supervisor remote controller, see
4
requirements"  [
  65] or refer to the remote controller installation and user
reference guide.
[2‑60]
0 (default)
1
[2‑65]
Automatic leak detection interval time.
This setting is used in conjunction with setting [2‑88].
[2‑65]
0 (default)
1
2
3
4
5
6
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
Description
In case the outdoor unit is installed in the highest
position (indoor units are installed on a lower position
than outdoor units) and the height difference between
the lowest indoor unit and the outdoor unit exceeds
50 m, the setting [2‑49] has to be changed to 1.
combinations" [
Description
Direct connection to the outdoor unit is not possible
Direct connection to the outdoor unit is allowed
Description
No supervisor remote controller connected to the
system
Supervisor remote controller connected to system
Time between automatic leak detection executions
4
 98].
"16.2  System layout
[days]
365
180
90
60
30
7
1
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12