18.2.10 To connect the multi connection piping kit

RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
NOTICE
Precautions when connecting field piping. Add brazing material as shown in the
figure.
≤Ø25.4
1
1
NOTICE
Be sure to use the supplied accessory pipes when carrying out piping work in the
field.
Be sure that the field installed piping does not touch other pipes, the bottom
panel or side panel. Especially for the bottom and side connection, be sure to
protect the piping with suitable insulation, to prevent it from coming into contact
with the casing.
Connect the stop valves to the field piping using the accessory pipes supplied with
the unit.
The connections to the branch kits are the responsibility of the installer (field
piping).
NOTICE
Improper installation may lead to malfunction of the outdoor unit.
Install the joints horizontally, so that the caution label (a) attached to the joint
comes to the top.
-
Do not tilt the joint more than 7.5° (see view A).
-
Do not install the joint vertically (see view B).
a
a Caution label
NOT allowed
Allowed
Make sure that the total length of the piping connected to the joint is absolute
straight for more than 500  mm. Only if a straight field piping of more than
120 mm is connected, more than 500 mm of straight section can be ensured.
>Ø25.4
1
2
2
1
7.5°
A
7.5°
a
18
Piping installation
|
B
Installer and user reference guide
109