Troubleshooting
Main
Sub code
code
Master Slave 1
Installer and user reference guide
180
Cause
Low pressure malfunction:
Stop valve closed
Refrigerant shortage
Indoor unit malfunction
Electronic expansion valve
malfunction (upper heat exchanger)
(Y1E) – main PCB (X21A)
Electronic expansion valve
malfunction (inverter cooling) (Y5E)
– main PCB (X23A)
Electronic expansion valve
malfunction (lower heat exchanger)
(Y3E) – main PCB (X22A)
Electronic expansion valve
malfunction (receiver gas) (Y4E) –
main PCB (X25A)
Electronic expansion valve
malfunction (subcool heat
exchanger) (Y2E) – main PCB (X26A)
Electronic expansion valve
malfunction (liquid injection)(Y7E)
- sub PCB (X9A)
Discharge temperature too high
(R21T) – main PCB (X33A):
Stop valve closed
Refrigerant shortage
Compressor casing temperature too
high (R15T) – main PCB (X33A):
Stop valve closed
Refrigerant shortage
Refrigerant overcharge
Stop valve closed
Ambient temperature sensor
malfunction (R1T) – main PCB
(X18A)
Solution
Open stop valves.
Check
refrigerant
+recharge unit.
Check the user interface's display
or
interconnection
between the outdoor unit and the
indoor unit.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Open stop valves.
Check
refrigerant
+recharge unit.
Open stop valves.
Check
refrigerant
+recharge unit.
Check
refrigerant
+recharge unit.
Open stop valves.
Check connection on PCB or
actuator.
SVEO
SVS
(a)
(b)
amount
wiring
amount
amount
amount
RYMA5+RXYA8~20A7Y1B