Venting Requirements - Victory CYCLONE Installation Manual And User's Manual

Professional bbq range hood
Hide thumbs Also See for CYCLONE:
Table of Contents

Advertisement

Vent system must terminate to the outside (roof or side wall).
DO NOT terminate the vent system in an attic or other enclosed area.
DO NOT use 4" (10.2 cm) laundry-type wall caps.
Use metal/aluminum vent only. Rigid metal/aluminum vent is recommended.
DO NOT use plastic vent.
Always keep the duct clean to ensure proper airflow.
Calculate the following figures before installation:
1. Distance from the floor to the ceiling.
2. Distance between the floor to the countertop/stove.
3. Distance between the countertop/stove to the range hood.
4. Height of hood and duct cover.
For the most efficient & quiet operation:
A distance of maximum 38" is recommended* between stove top and the top of the range hood
filters.
It is recommended that the range hood be vented vertically through the roof through 8" or bigger
round metal/aluminum vent work.
The size of the vent should be uniform.
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent between the elbows if more than one
elbow is used.
DO NOT install two elbows together.
The length of vent system and number of elbows should be kept to a minimum to provide efficient
performance.
The vent system must have a damper. If roof or wall cap has a damper, DO NOT use damper (if
supplied) on top of the range hood.
Use aluminum tape to seal all joints in the vent system.
Use caulking to seal exterior wall or roof opening around the cap. USE 8" ROOF OR WALL VENT
CAP MINIMUM.
IMPORTANT:
A minimum of a 8" round duct (standard for this range hood) must be used to maintain maximum
airflow efficiency. There is also an option to use an 10" round duct size for this unit.
Always use rigid type metal/aluminum ducts if available to maximize airflow when connecting to
provided duct.
Please use Duct Run Calculation below to compute total available duct run when using elbows,
transitions and caps.
ALWAYS, when possible, reduce the number or transitions and turns in the duct run. If a long duct
run is required, increase the duct size from 8" to 10". If a reducer is used, install a long reducer
instead of a pancake reducer. Reducing the duct size will restrict airflow and decrease efficiency.
If turns or transitions are required: Install as far away from opening and as far apart, between 2, as
possible.
Minimum mount height between stove top to hood bottom should be no less than 30-inch*.
Maximum mount height between stove top to hood bottom should be no higher than 36-inch*.
It is important to install the hood at the proper mounting height. Hoods mounted too low could
result in heat damage and fire hazard; while hoods mounted too high will be hard to reach and will
loose its performance and efficiency.
If available, also refer to stove top manufacturer's height clearance requirements and
recommended hood mounting height above range.
Minimum Duct Size:
Round - 8" minimum
Round - 10" recommended/optional
6
| CYCLONE

VENTING REQUIREMENTS

* Due to different ceiling height configurations, recommended height may not be applicable.