System Inlet Temperature, Extended Ambient Operating Support
Specification
System Inlet Temperature, Extended Ambient Operating
Support
—
—
1
System performance may be reduced if operating in the extended ambient operating range or with a fan fault.
The approved hardware configurations for this system are listed on the Hewlett Packard Enterprise website.
Mechanical specifications
Specification
Height
Depth
Width
Weight (maximum)
Weight (minimum)
Power supply specifications
Depending on installed options, the server is configured with one of the following power supplies:
•
HPE 800W Flex Slot Platinum Hot-plug Low Halogen Power Supply
HPE 800W Flex Slot -48VDC Hot-plug Low Halogen Power Supply
•
HPE 1600W Flex Slot Platinum Hot-plug Low Halogen Power Supply
•
For detailed power supply specifications, see the QuickSpecs on the Hewlett Packard Enterprise website (http://
www.hpe.com/info/proliant/powersupply).
162
Specifications
Value
—
For approved hardware configurations, the supported system
inlet range is extended to be 5°C to 10°C (41°F to 50°F) and
35°C to 40°C (95°F to 104°F)
All temperature ratings shown are for sea level with an
altitude derating of 1.0 °C per every 175 m (1.8°F per every
574 ft) above 900 m (2953 ft) to a maximum of 3050 m
1
(10,000 ft).
For approved hardware configurations, the supported system
inlet range is extended to be 40°C to 45°C (104°F to 113°F)
All temperature ratings shown are for sea level with an
altitude derating of 1.0 °C per every 125 m (1.8°F per every
410 ft) above 900 m (2953 ft) to a maximum of 3050 m
1
(10,000 ft).
Value
17.48 cm (6.88 in)
75.18 cm (29.60 in)
44.55 cm (17.54 in)
51.71 kg (114 lbs)
28.12 kg (62 lbs)