Electrical connection
6.3 Connecting the grounding conductor
6.3.2
Grounding connection type
Type of enclosure grounding
Connection of an individual conductor under
the external grounding bracket.
Connection is made using a DIN cable lug under
the external grounding bracket. DIN 46 234
Internal ground terminal
Comply with the following instructions when connecting up:
• Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
• Arrange the spring lock washer under the screw head.
• Locate the cable lug under the clamping bracket.
• Use the terminals designated for the grounding conductor in the terminal box.
• Observe the tightening torque (Page 168) for the locking screw.
External ground terminal
Comply with the following instructions when connecting up:
• Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
• Locate the cable lug between the contact bracket and the grounding bracket; do not
remove the contact bracket pressed into the enclosure.
• Arrange the flat washer and spring washer under the bolt head.
• Use the marked connection location for the grounding conductor on the stator housing.
• Observe the tightening torque (Page 168) for the locking screw.
92
Conductor cross-
1MB1.33 Eagle Line shaft heights 71 ... 315
Operating Instructions, 08/2023, A5E52990459A
section
mm²
... 10
... 25