Cable glands with connecting thread in the terminal box (EN 50262)
6.2
Tightening torques
Note the information in Chapter Tightening torques (Page 167).
6.3
Connecting the grounding conductor
The machine's grounding conductor cross-section must comply with EN / IEC 60034-1.
Please also observe installation regulations such as those specified in EN / IEC 60204-1.
Basically, there are two ways of connecting a grounding conductor to the machine.
• Internal grounding with a connection in terminal box at the location intended for this
purpose and marked accordingly.
• External grounding with connection at the stator housing at the locations intended for
this purpose and marked accordingly.
6.3.1
Minimum surface area of grounding conductor
Table 6- 2
Minimum cross-section of the phase conductor
1MB1.33 Eagle Line shaft heights 71 ... 315
Operating Instructions, 08/2023, A5E52990459A
Minimum cross-sectional area of grounding conductor
for installation
S
mm²
S ≤ 25
25 < S ≤ 50
S > 50
②
O ring
Minimum cross-section of the associated
grounding connection
mm²
0.5 S
Electrical connection
6.2 Tightening torques
S