Burner Refitting; Pump; Pump Priming - Riello RLS 38/E Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burners
Table of Contents

Advertisement

4.8

Burner refitting

➤ Refit the burner 4)(Fig. 16) to the slide bars 3) at approxi-
mately 4" from the sleeve 5) - burner positioned as shown in
(Fig. 11 at page 19);
➤ insert the ignition electrode cables and then slide bars the
burner up to the sleeve so that it is positioned as shown in
Fig. 16;
➤ remove extention bars.
➤ refit screws 2) on slide bars 3);
4.9

Pump

Pump model SUNTEC AL 65
Min. delivery rate at 174 PSI pressure
Delivery pressure range
Max. suction pressure
Viscosity range
Max light oil temperature
Max. suction and return pressure
Pressure calibration in the factory
Filter mesh width
Installation
2
4
1
GPH
21.5
PSI
58 - 261
"Hg
13
cSt
2 - 12
°F
140 - 60
PSI
29
PSI
174
inch
0.006
D2542
Fig. 17
➤ secure the burner to the sleeve by tightening screw 1);
➤ connect the oil pipes again by screwing on the two connectors
4)(Fig. 11 at page 19).
NOTE:
when fitting the burner on the two slide bars, it is advisable to gently
draw out the high tension cables until they are slightly stretched.
5
3
Legend (Fig. 17)
1
Suction
2
Return
3
Pressure gauge attachment
4
Vacuum gauge attachment
5
Pressure regulator
4.9.1

Pump priming

Before starting the burner, make sure that the tank
return line is not clogged.
Obstructions in the line could cause the seal located
WARNING
on the pump shaft to break (the pump leaves the
factory with the by-pass closed).
➤ Also check to make sure that the valves located on the suction
line are open and that there is sufficient fuel in the tank.
➤ For self-priming to take place, one of the screws 3)(Fig. 17) of
the pump, must be loosened in order to bleed off the air con-
tained in the suction line
➤ Start the burner by closing the control circuit in the manual
position and switch in the "OIL" position.
➤ The pump is primed when the fuel oil starts coming out of the
screw 3)(Fig. 17).
➤ Stop the burner.
The time required for this operation depends upon the diameter
and length of the suction tubing. If the pump fails to prime at the first
starting of the burner and the burner locks out, reset the burner,
and then repeat the starting operation.
Do not illuminate the UV scanner cell or the burner will lock out.
21
GB
6
D10466
1/4" NPT
1/4" NPT
G 1/8"
G 1/8"
Fig. 16
20027066

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 50/eC9333453C9333400C9333410C933340120110085

Table of Contents