Burner Start-Up; Adjusting Gas/Air Delivery; Adjusting Oil/Air Delivery - Riello RLS 38/E Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burners
Table of Contents

Advertisement

5.4

Burner start-up

Feed electricity to the burner via the disconnecting switch on the
boiler panel.
Close the thermostats/pressure switches, set the parameters on
the RWF 55 regulator. Please refer to the spacific manual for this
operation.
Turn the switch to position "ON" (Fig. 31) and turn the switch of to
position "LOCAL" and turn the switch to position "OIL" for oil oper-
ation and "GAS" for gas operation.
Make sure that the lamps or testers connected to
the solenoids, or indicator lights on the solenoids
themselves, show that no voltage is present.
DANGER
If voltage is present, stop the burner immediately
and check the electrical wiring.
When the burner starts, check the direction of the
motor rotation, as indicated in Fig. 31.
As the burner is not fitted with a device to check the
sequence of the phases, the motor rotation may be
incorrect.
As soon as the burner starts up, go in front of the
cooling fan of the fan motor and check it is rotating
anticlockwise.
If this is not the case:
➤ place the switch in position "0" and wait for the
control box to carry out the switch-off phase;
➤ disconnect the electrical supply from the
burner;
➤ invert the phases on the three-phase power
supply.
20027066
Start-up, calibration and operation of the burner
OFF
ON
LOCAL REMOTE
OIL OFF GAS
D10806
5.4.1

Adjusting gas/air delivery

➤ Move slowly towards the maximum output (but-
terfly gas valve completely open);
➤ adjust the required maximum output with the
DANGER
gas pressure stabilizer;
➤ adjust the combustion parameters with the air
servomotor and store the maximum combus-
tion point.
Complete the procedure slowly, synchronizing the
combustion with the two servomotors and storing
the different setting points.
For the start-up procedure and the parameters
calibration, refer to the specific instruction man-
ual of the
with the burner.
WARNING
5.4.2

Adjusting oil/air delivery

For the start-up procedure and the parameters
calibration, refer to the specific instruction man-
ual of the
WARNING
with the burner.
28
GB
LMV36.5...
electronic cam supplied
LMV36.5...
electronic cam supplied
Fig. 31