Legend to sequence diagrams (Fig. 7 and Fig. 8)
Valve proving takes place depending on the parameter:
Between phase 62 and phase 70 or / and between phase 24 and
phase 30
1
Parameter:
Short / long preignition time for oil only
Short / long oil pump – switch-on time – time
2
Only with valve proving on startup
3
Parameter: With / without alarm in the event of prevention of
startup
4
In the event of an erroneous signal on startup, followed by
phase 10, otherwise phase 70
5
27 s = maximum time safety phase, followed by lockout
6
5 s = time between occurrence of prevention of startup and
indication
7
Only with valve proving on startup (valve proving via pressure
switch-min)
8
Only in case of startup without valve proving (valve proving
via pressure switch-min)
9
Inverse logic in case of valve proving via pressure switch-min
10 Parameter:
Oil pressure min input
1 = active from phase 38
2 = active from safety time
11 Only with fuel train Lo with 2 fuel valves
Assignment of times:
t1
Prepurge time
TSA
Safety time
Permissible position range
In standby: the actuator can travel within the permissible
positioning range, but is always driven to the no-load po-
sition. When changing phases, it must be in the no-load
position.
0° / 10%
Position as supplied (0°)
90° / 100%
Actuator fully open (90°)
AL
Alarm
FS
Flame signal
LP
Air pressure switch
M
Fan motor N Postpurging
P LT
Valve proving (pressure switch)
Pmin
Pressure switch-min
Pmax
Pressure switch-max
POC
Proof of closure
PV
Pilot valve
SA...
Actuator
SB
Safety limiter
SV
Safety shutoff valve
STB
Safety limit thermostat
V
Prepurging
V...
Fuel valve
Signal ON
Signal OFF
Permissible signal
20027066
Technical description of the burner
16
GB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 50/eC9333453C9333400C9333410C933340120110085