Data Setting And Programming Examples; Data Settings - Omron SYSMAC C200H-DA002 Operation Manual

Analog i/o units
Hide thumbs Also See for SYSMAC C200H-DA002:
Table of Contents

Advertisement

Data Setting and Programming Examples

2-4

Data Setting and Programming Examples

2-4-1 Data Settings

Basic Settings
Item
Unit number 0 (allocated words: IR 100 to IR 109 and DM 1000 to DM 1043)
Inputs used
Inputs 1 to 5 (The conversion prohibit bits for inputs 6 to 8 are turned ON.)
A/D
BCD
conversion
data
Detailed Settings
Item
Input signal range
Scaling function Lower limit
Upper limit
Number of terms for mean
value calculation
Square root function
Limit warning
Mode
function
Lower limit
Upper limit
DM Area Settings
DM word
Contents
DM 1000
03E0
DM 1001
006A
DM 1002
0704
DM 1003
0102
DM 1004
1000
DM 1005
5000
DM 1006
1000
DM 1007
5000
DM 1008
0400
DM 1009
1000
DM 1022
0050
DM 1030
1200
DM 1031
4800
30
The following settings are used in this example.
Input 5
Input 4
–10 to +10 V
0 to +10 V
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Data in the DM area is set using a computer running SSS, a Programming Con-
sole, or other Peripheral Device.
After setting the data, turn the PC ON → OFF→ ON or turn AR 0100 (the Spe-
cial I/O Unit Restart Bit) OFF→ ON → OFF to initialize the Unit with the new set-
tings.
Limit warning mode (bit 09 = "1"), BCD (bit 08 = "1"), conversion prohibit (bits 05 to 07 = "1")
Input signal range setting (00 00 00 00 01 10 10 10)
Scaling function (bits 08 to 10 = "1"), mean value function (bit 02 = "1")
Square root function (bit 08 = "1"), limit warning function (bit 01 = "1")
Input 1 lower limit for scaling
Input 1 upper limit for scaling
Input 2 lower limit for scaling
Input 2 upper limit for scaling
Input 3 lower limit for scaling
Input 3 upper limit for scaling
Input 3 number of terms for mean value
Input 2 limit warning function: lower limit
Input 2 limit warning function: upper limit
Setting
Input 3
4 to 20 mA
1 to 5 V
0400
1000
1000
5000
50
---
---
---
---
2
---
1200
---
4800
Data
Section 2-4
Input 2
Input 1
1 to 5 V
1000
5000
---
Yes
---
---
---

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac c200hsSysmac c200h-ad002Sysmac c200h

Table of Contents