Emerson 475 User Manual page 89

Field communicator
Hide thumbs Also See for 475:
Table of Contents

Advertisement

Troubleshooting
Function Block Service Error:
Parameter Check
Function Block Service Error:
Exceeds Parameter Limits
Function Block Service Error: Wrong
Mode For Request
SM ERROR: REMOTE ERROR
INVALID STATE
FF Library System Management
Error. SM Set Address Failed.SM
Error SM ERROR: Failed.
RESPONDER IDENTIFY
or
Fieldbus Library error code -49
FBLIB: Address outside of range set
in Field Communicator.
The parameter value being
entered is invalid for this device.
Check with the device supplier.
Make sure the value entered is
valid for that specific device
parameter.
The parameter value being
entered is outside the range of
valid values for the device
parameter. Check with the device
supplier. Make sure the value
entered is in the correct range for
that device parameter.
The block is in the wrong mode to
accept the parameter change
being requested. See "Change
modes" on page 68 for information
on how to change block modes.
An attempt to change the address
of the device serving as the LAS
on the segment is being made.
Changing the device address of
the LAS is not recommended.
These messages typically occur
when there is an error changing a
device address.
Possible solutions:
1.Make sure the 475 Field
Communicator is the LAS. Some
LASs may not let you change the
device address.
2. Make sure the address is not
already used by another device.
3. Make sure the polling range is
set to poll the device address.
89

Advertisement

Table of Contents
loading

Table of Contents