Removing shrouds

1.
Open the door of the incoming cubicle.
2.
Remove the shrouding and assembly plates covering the input terminals.

Connecting the cables

This section describes the power cable connecting procedure for a bottom cable entry
with the standard cable entry plate. The standard cable entry plate has conductive
sleeves for the 360 degree grounding of the cable shields. If the drive or unit has
another type of cable entry plate, such as a Roxtec cable entry plate (option +H394),
or cable gland plate (option +H358), refer also to the instruction of the related non-ABB
installation accessories. For example, the Roxtec instructions or the instructions by
the cable gland manufacturer.
1.
IP54 cabinet: Remove the rear horizontal cable support and the cable entry plate.
2.
IP54 cabinet: Remove a sealing grommet from the cable entry plate for each cable.
Cut hole into the rubber grommet and slide it onto the cable.
1
3.
Lead the cables inside the cabinet through the cable entry plate. If there are several
cables, use the rear 3 holes first.
Electrical installation 53
2
2
11