Derating

Surrounding air temperature derating

In the temperature range +45...55 °C (+113...131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
calculated by multiplying the current given in the rating table by the derating factor
(k) :
k
1.00
0.95
0.90
+45 °C
+113 °F

Altitude derating

At altitudes more than 1000 m (3281 ft) above sea level, the output current derating
is 1 percentage point for every added 100 m (328 ft). For example, the derating factor
for 1500 m (4921 ft) is 0.95. The maximum permitted installation altitude is given in
the technical data.
For a more accurate derating, use the DriveSize PC tool.

Coolant temperature derating

See section
Temperature limits (page

Antifreeze content derating

See section
Temperature limits (page

Switching frequency derating

Switching frequencies other than default can require output current derating. Contact
ABB for more information.