9.
Remove the module retaining screws at the top and the bottom of the module.
10. Pull the module carefully out onto the service platform. Keep the module secured
to a hoist or equivalent to prevent the module from falling. For information on
using the lifting device, see
hardware manual (3AXD50000210268
Reinstalling the module
1.
Push the module carefully into its bay.
2.
Fasten the retaining screws at the top and the bottom of the module.
3.
Reinstall the DC busbars at the top of the module.
4.
Reconnect the coolant pipes to the module. Tighten to specified torque. R8i module
coolant connections: 15 N·m (11.1 lbf·ft). Other connections: 20 N·m (14.75 lbf·ft).
5.
Reconnect the control wiring to the module.
Converter module lifting device for drive cabinets
[English]).
Maintenance 117