Installation Procedure
• Install the unit in a place where water can drain smoothly.
• If you have any difficulty finding installation location as
prescribed above, contact your manufacturer for details.
• Consider that the salinity particles clinging to the
external panels should be sufficiently washed out. Be
sure to clean sea water and dust from the outdoor unit
heat exchanger and apply a corrosion inhibitor on it at
least once a year.
• Because the residual water at the bottom of the
outdoor unit significantly promotes corrosion, make
sure that the slope does not disturb drainage.
‐ Keep the floor level so that rain does not accumulate.
‐ Be careful not to block the drain hole due to foreign
substance.
• Check the condition of the product periodically.
‐ Check the installation site every 3 months and
perform anti-corrosion treatment such as R-Pro
supplied by SAMSUNG (Code : MOK-220SA) or
commercial water repellent grease and wax, etc.,
based on the product condition.
‐ When the product is to be shut down for a long
period of time, such as off-peak hours, take
appropriate measures like covering the product.
• If the product installed within 1640.4 ft (500 m) of
seashore, special anti-corrosion treatment is required.
※ Please contact your local SAMSUNG
representative for further details.
CAUTION
• In areas with heavy snow fall, piled snow could block
the air intake. To avoid this incident, install a frame
that is higher than estimated snow fall. In addition,
install a snow-proof hood to avoid snow from piling on
the outdoor unit.
Estimated
snow fall
6
English
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 6
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 6
Snow-proof hood
Frame
Ground
Minimum clearances for the outdoor unit
When installing 1 outdoor unit
11.81 (300)
23.62 (600)
or more
or more
11.81 (300)
or more
Unit: inch (mm)
78.74 (2000)
or more
2023-09-22 오후 1:46:53
2023-09-22 오후 1:46:53