1 Turn on the outdoor unit, and then check whether the display 1/2 indications are displayed "E199" code.
※ During the initial , display 1 shows "
• If different display code is shown, see Troubleshooting on page 34 and take corrective actions.
2 Push once the K1 button.
3 After the operations described above have been performed, the system starts in Cooling or Heating mode,
depending on the external ambient temperature. After a few minutes (from a minimum of 3 to 5 minutes for the
internal unit), the system stops automatically, completing the self-test and addressing procedure. "
on the display of the outdoor unit.
4 If you press the K1 button one more time, "
NOTE
• At this point it is possible to start the internal units in the desired mode.
※ If "
"doesn't display, the procedure has failed and it is therefore necessary to read ALL the operator's manual
before repeating the operating described in steps 1-2-3-4.
Setting an indoor unit address (MAIN/RMC)
1 Check whether power is supplied or not.
‐ When the indoor unit is not plugged in, there
should be additional power supply in the
indoor unit.
2 The panel (display) should be connected to an indoor unit to receive option.
3 Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
4 Assign an indoor unit address by wireless remote controller.
‐ The initial setting status of indoor unit ADDRESS(MAIN/RMC) is "0A0000-100000-200000-300000"
‐ There is no need to assign extra ADDRESS for 1:1 installation between indoor unit and outdoor unit.
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 29
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 29
" and display 2 shows the connected indoor number.
" disappears and inspection is complete.
" appears
Indoor Unit
1(L)
F2
2(N)
F1
29