Technical specifications
Article number
Input current
•
Input delay (for rated value of input voltage)
for standard inputs
Cable length
•
Digital outputs
Number of digital outputs
•
Short-circuit protection
•
Limitation of inductive shutdown voltage to
Controlling a digital input
Switching capacity of the outputs
•
Load resistance range
•
•
Output current
•
•
•
Output delay with resistive load
•
•
Parallel switching of two outputs
•
•
Switching frequency
•
•
•
Total current of the outputs
•
•
Cable length
•
76
for signal "1", typ.
–
parameterizable
unshielded, max.
in groups of
Response threshold, typ.
on lamp load, max.
lower limit
upper limit
for signal "1" rated value
for signal "1" permissible range, max.
for signal "0" residual current, max.
"0" to "1", max.
"1" to "0", max.
for uprating
for redundant control of a load
with resistive load, max.
with inductive load, max.
on lamp load, max.
Current per group, max.
Current per module, max.
unshielded, max.
CM 8x IO-Link + DIQ 8x24VDC M12-L 8xM12 (6ES7148-6JJ00-0BB0) communications module
6ES7148-6JJ00-0BB0
2.5 mA
Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
30 m
8; Parameterizable as DIQ
8
Yes; per channel, electronic
0.5 A: 1 A
0.5 A: typ. 1L+ (-70 V)
Yes
5 W
48 Ω
4 kΩ
0.5 A
0.5 A
0.1 mA
50 µs
100 µs
No
Yes
100 Hz
0.5 Hz
1 Hz
1L+: 4 A
4 A
30 m
Equipment Manual, 12/2022, A5E51718265-AB