Update time of the I/O data

You can estimate the typical update time for an I/O cycle as follows:
Update time (can be set starting at 2 ms)
+ I/O processing (typically 1.4 ms, +/- 1 ms jitter due to free-running cycles)
+ EM conversion (dependent on cycle time and parameter assignment of the module)
If necessary, you must take into account other influences caused by the MTCP client and
network components by adding them.