Service/special operation
PStick command
0: No operation | 1: Reading from stick | 2: Writing on stick
PStick progress
PStick status
0: No stick | 1: Stick ready | 2: Writing on stick | 3: Reading from stick | 4: EMC
test active | 5: Writing error | 6: Reading error | 7: Incompatible data set | 8:
Wrong stick type | 9: Stick format error | 10: Check data set | 11: Data set
disabled | 12: Reading disabled
Config extension module
Function extension module 1
0: None | 1: Multifunctional | 2: Heating circuit 1 | 3: Heating circuit 2 | 4: Heating
circuit 3 | 6: Solar DHW | 7: Primary contr/system pump
Relay output QX21 module 1
0: None | 1: Circulating pump Q4 | 2: El imm heater DHW K6 | 3: Collector pump
Q5 | 4: Cons circuit pump VK1 Q15 | 5: Boiler pump Q1 | 7: Alarm output K10 |
11: Heat circuit pump HC3 Q20 | 12: Cons circuit pump VK2 Q18 | 13: System
pump Q14 | 14: Heat gen shutoff valve Y4 | 15: Solid fuel boiler pump Q10 | 16:
Time program 5 K13 | 17: Buffer return valve Y15 | 18: Solar pump ext exch K9 |
19: Solar ctrl elem buffer K8 | 20: Solar ctrl elem swi pool K18 | 22: Swimming
pool pump Q19 | 25: Cascade pump Q25 | 26: St tank transfer pump Q11 | 27:
DHW mixing pump Q35 | 28: DHW interm circ pump Q33 | 29: Heat request K27
| 33: Heat circuit pump HC1 Q2 | 34: Heat circuit pump HC2 Q6 | 35: DHW ctrl
elem Q3 | 40: Status output K35 | 41: Status information K36 | 43: Fan
shutdown K38
Relay output QX22 module 1
See
Parameters see Relay output QX21 module 1 (prog. no.
7301)!
Relay output QX23 module 1
See
Parameters see Relay output QX21 module 1 (prog. no.
7301)!
Sensor input BX21 module 1
0: None | 1: DHW sensor B31 | 2: Collector sensor B6 | 4: DHW circulation
sensor B39 | 5: Buffer sensor B4 | 6: Buffer sensor B41 | 8: Common flow
sensor B10 | 9: Solid fuel boiler sensor B22 | 10: DHW charging sensor B36 |
11: Buffer sensor B42 | 12: Common return sensor B73 | 13: Cascade return
sensor B70 | 14: Swimming pool sensor B13 | 16: Solar flow sensor B63 | 17:
Solar return sensor B64
Sensor input BX22 module 1
See
Parameters see Sensor input BX21 module 1 (prog. no. 7307)!
Function input H2/H21 module 1
0:None | 1: Optg mode change HCs+DHW | 2: Optg mode changeover DHW |
3: Optg mode changeover HCs | 4: Optg mode changeover HC1 | 5: Optg mode
changeover HC2 | 6: Optg mode changeover HC3 | 7: Heat generation lock | 8:
Error/alarm message | 9: Consumer request VK1 | 10: Consumer request VK2 |
11: Release swi pool source heat | 12: Excess heat discharge | 13: Release swi
pool solar | 14: Operating level DHW | 15: Operating level HC1 | 16: Operating
level HC2 | 17: Operating level HC3 | 18: Room thermostat HC1 | 19: Room
thermostat HC2 | 20: Room thermostat HC3 | 22: DHW thermostat | 25: Limit
thermostat HC | 29: Start prevention | 51: Consumer request VK1 10V | 52:
Consumer request VK2 10V | 58: Output request 10V
Contact type H2/H21 module 1
0: NC | 1: NO
Input value 1 H2/H21 module 1
Funct value 1 H2/H21 module 1
7713465 - 05 - 23102019
Prog. no.
Level
Standard value
7252
E
0: No operation
7253
E
0%
0: No stick
Prog. no.
Level
Standard value
7300
C
3: Heating circuit 2
7301
C
0: None
7302
C
0: None
7303
C
0: None
7307
C
0: None
7308
C
0: None
7321
C
0:None
7322
C
1: NO
7324
C
0 V
7325
C
0
9 Settings