Input/Output Test; Status - Potterton Eurocondense five 400 kW Installation Manual

Gas condensing boiler
Table of Contents

Advertisement

7713465 - 05 - 23102019
Boiler pump Q1: The connected pump is used for recirculation of the
boiler water.
DHW pump Q3: Actuator for DHW storage tank.
DHW interm circ pump Q33: Actuation of a charge pump for domestic
hot water storage with external heat exchanger.
Heat circuit pump HC1 Q2/Heat circuit pump HC2 Q6/Heat circuit pump
HC3 Q20: Activation of the pump heating circuits HC1-HC3.
Collector pump Q5: Actuation of a circulating pump when a solar
collector is used.
Solar pump ext exch K9: The solar circuit pump for the external heat
exchanger K9 must be set here.
Solar pump buffer K8: If several exchangers are connected, the buffer
storage tank must be set at the respective relay output and the type of
solar regulating unit must be defined under prog.no.5840.
Solar pump swi pool K18: If several exchangers are connected, the
swimming pool must be set at the respective output and the type of the
solar regulating unit must be defined in prog.no. 5840.
Sign logic out UX21 module1 (7349), Sign logic out UX22
module1 (7356), Sign logic out UX21 module2 (7424), Sign logic
out UX22 module2 (7431), Sign logic out UX21 module3 (7499),
Sign logic out UX22 module3 (7506)
Output UX21/22 can be inverted when output if the output signal is
configured as PWM. This means that variable-speed pumps can also be
actuated using inverted signal logic
Signal output UX21 module 1 (7350), Sign logic out UX22
module1 (7357), Signal output UX21 module 2 (7425) and Signal
output UX22 module 2 (7432), Signal output UX21 module 3
(7500) und Signal output UX22 module 3 (7507)
Specifies whether the signal is to be output as a 0 - 10 V signal or pulse-
width modulated (PWM) signal.
9.2.23

Input/output test

Input/output tests
Tests for checking the function of connected components.
9.2.24

Status

State
With this function the status of the selected system can be requested.
Tab.20
Status table heating circuit
The following messages are possible under Heating circuit:
End user (Eu)
Limiter has tripped
Manual control active
Floor curing function active
Heating mode restricted
Forced draw
Comfort heating mode
Commissioning, Engineer (menu
Status)
Limiter has tripped
Manual control active
Floor curing function active
Overtemp prot active
Restricted, boiler protection
Restricted, DHW priority
Restricted, buffer
Forced draw DHW
Forced draw source
Overrun active
Opt start ctrl+boost heating
Optimum start control
9 Settings
135