9 Settings
Tab.17
Check no. storage tank (prog.-no. 6215)
Domestic water storage tank
No buffer storage tank
Buffer storage tank
Buffer storage tank, heat generation shutoff valve
Buffer storage tank, solar connection, source shut-off
valve
Tab.18
Check no. heating circuit (prog.-no. 6217)
Heating circuit 3
0
No heating circuit
1
DHW circulation via boiler circuit
pump
2
Heating circuit pump
3
Heating circuit pump, mixer
126
0
No DHW storage tank
1
Immersion heater
4
Primary pump
5
Charging pump, solar connection
13
Diverter valve
16
Primary controller, without heat exchanger
17
Primary controller, 1 heat exchanger
Heating circuit 2
00
No heating circuit
01
DHW circulation via boiler circuit
pump
02
Heating circuit pump
03
Heating circuit pump, mixer
Software version (6220)
Display of the actual software version.
Info 1 OEM(6230), Info 2 OEM (6231), Info 3 OEM (6258), Info
4 OEM (6259) and Parameter set number OEM (6236)
These parameters are EEPROM storage locations that may contain
information from the OEM.
9.2.18

LPB system

Device address (6600) andSegment address (6601)
The two-part LPB address of the controller consists of the 2-digit segment
number and the 2-digit device number.
Bus power supply function (6604)
Off: The controller does not provide the bus power supply.
Automatically: The bus power supply is switched on and off by the
controller in accordance with the power demand of the bus system.
Bus power supply state (6605)
Off: The bus system power supply by the controller is currently inactive.
On: The bus system power supply by the controller is currently active.
Display system messages (6610)
This setting allows system messages which are transmitted via LPB to be
suppressed on connected operating elements.
System message to alarm relay (6611)
No: Alarm output K10 Is not triggered when a system fault is reported.
Yes: Alarm output K10 Is triggered when a system fault is reported.
Alarm delay (6612)
The transmission of the alarm to the BM module can be delayed in the
basic device by an adjustable time. This allows the prevention of
unnecessary messages to a service location caused by malfunctions
which only occur briefly (e.g. temperature monitor queried, communication
errors). However, it must be noted that malfunctions which occur briefly
and quickly re-occur are also filtered out by this.
Heating circuit 1
00
No heating circuit
01
DHW circulation via boiler circuit
pump
02
Heating circuit pump
03
Heating circuit pump, mixer
7713465 - 05 - 23102019