6
|
Application guidelines
6.5.4 Preferential kWh rate power supply
Installer reference guide
60
▪
Connection and setup:
-
Connect the second power meter to X15M/9 and X15M/10. See
connect the electricity
-
In the software the power consumption data of both meters is added so you do
NOT have to set which meter covers which power consumption. You only need
to set the number of pulses of each power meter.
▪
See
"6.5.4 Preferential kWh rate power
power meters.
General rule
▪
Power meter 1: Measures the outdoor unit.
▪
Power meter 2: Measures the rest (i.e. indoor unit and backup heater).
Setup
▪
Connect power meter 1 to X15M/5 and X15M/6.
▪
Connect power meter 2 to X15M/9 and X15M/10.
See
"9.3.6 To connect the electricity
Power meter types
▪
Power meter 1: Single- or three-phase power meter according to the power
supply of the outdoor unit.
▪
Power meter 2:
-
In case of a single-phase backup heater configuration, use a single-phase
power meter.
-
In other cases, use a three-phase power meter.
Example
Single-phase outdoor unit with a three-phase backup heater:
0
0
58 0
1 5 0
a
c
e
e
f
g
h
i
A
B
A Outdoor unit
B Indoor unit
a Electrical cabinet (L
b Electrical cabinet (L
c Power meter (L
d Power meter (L
e Fuse (L
/N)
1
f Fuse (L
/L
/L
1
2
g Outdoor unit (L
h Indoor unit (L
i Backup heater (L
4
meters" [
126].
supply" [
4
meters" [
0
0
58 0
1 5 0
b
d
/N): Preferential kWh rate power supply
1
/L
/L
/N): Normal kWh rate power supply
1
2
3
/N)
1
/L
/L
/N)
1
2
3
/N)
3
/N)
1
/N)
1
/L
/L
/N)
1
2
3
4
60] for an example with two
126].
EPRA14~18DAV3+W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02