Daikin ETSHB16P50EF Installation Manual

Daikin ETSHB16P50EF Installation Manual

Hide thumbs Also See for ETSHB16P50EF:
Table of Contents

Advertisement

Quick Links

Installation manual
Daikin Altherma 3 H HT ECH₂O
https://daikintechnicaldatahub.eu
ETSH16P30EF
ETSH16P50EF
ETSHB16P30EF
ETSHB16P50EF
ETSX16P30EF
ETSX16P50EF
Installation manual
ETSXB16P30EF
English
Daikin Altherma 3 H HT ECH₂O
ETSXB16P50EF

Advertisement

Table of Contents
loading

Summary of Contents for Daikin ETSHB16P50EF

  • Page 1 Installation manual Daikin Altherma 3 H HT ECH₂O https://daikintechnicaldatahub.eu ETSH16P30EF ETSH16P50EF ETSHB16P30EF ETSHB16P50EF ETSX16P30EF ETSX16P50EF Installation manual ETSXB16P30EF English Daikin Altherma 3 H HT ECH₂O ETSXB16P50EF...
  • Page 2 3P664373-4C...
  • Page 3: Table Of Contents

    6.3.10 To connect the changeover to external heat source... 22 6.3.11 To connect the power consumption digital inputs ..23 ▪ Format: Digital files on https://www.daikin.eu. Use the search 6.3.12 To connect the safety thermostat (normally closed function to find your model.
  • Page 4: Specific Installer Safety Instructions

    ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). WARNING ▪ The full set of latest technical data is available on the Daikin Fixing method of the indoor unit MUST be in accordance Business Portal (authentication required).
  • Page 5: About The Box

    WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 6: To Remove The Accessories From The Indoor Unit

    Heating Solutions Navigator which can be reached via https://professional.standbyme.daikin.eu. Please contact your dealer if you have no access to Heating Solutions Navigator. Screw plug Assembly wrench Handle Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 7: Opening And Closing The Unit

    3 Lower the switch box. Do NOT damage or remove the foam sealing of the switch box. 3 Disconnect the ground connection from the top cover of the switch box. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 8: To Close The Indoor Unit

    Ensure that the water level cannot mount above the overspill. 6 Connect the drain pan hose to the drain pan connection and connect to an appropriate drain. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 9: Piping Installation

    NOT Minimum required flow rate exceeded. The minimum water pressure to operate is 1  bar 12 l/min (=0.1 MPa). ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 10: Connecting Water Piping

    2 Remove the thermal insulation of the hydraulic block. Open the vent valve on the pump by one turn. Afterwards put the thermal insulation back on the hydraulic block. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 11 A pressure relief valve (field supply) with an opening pressure of maximum 10  bar (=1  MPa) must be installed on the domestic cold water inlet connection in accordance with the applicable legislation. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 12: To Connect A Pressure Vessel

    1 Connect a hose with a non-return valve (1/2") and an external manometer (field supply) to a water tap and the fill and drain valve. Secure the hose against slipping off. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 13: To Protect The Water Circuit Against Freezing

    ▪ The domestic hot water heat exchanger the system from bursting or from freezing. To prevent the system from freezing, more glycol is required. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 14: To Fill The Storage Tank

    Outdoor water piping insulation See the installation manual of the outdoor unit, or the installer reference guide. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 15: Electrical Installation

    "6.3.12 To connect the safety Wires: 2×0.75 mm² thermostat (normally closed contact)" [ 4  23]. [9.B.1]=2 (External sensor = Room) Smart Grid "6.3.13 To connect a Smart [1.7] Room sensor offset Grid" [ 4  24]. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 16: To Connect The Electrical Wiring To The Indoor Unit

    If the switch box is lowered in service position while the electrical installation is done, additional cable length has to be taken into account adequately. The cable routing in normal position is longer than in service position. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 17: To Connect The Main Power Supply

    2 Connect the main power supply. In case of normal kWh rate power supply Interconnection Wires: (3+GND)×1.5 mm² cable Power supply Wires: 1N+GND indoor unit Maximum running current: 6.3 A — ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 18: To Connect The Backup Heater Power Supply

    MUST be protected by the safety devices required by the applicable legislation. CAUTION To guarantee the unit is completely earthed, ALWAYS connect the backup heater power supply and the earth cable. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 19: To Connect The Backup Heater To The Main Unit

    1N~, 50 Hz 230 V AC 4 Top cover 2 Connect both connection cables from the backup heater EKECBU* to the appropriate connectors as shown in the illustration below. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 20: To Connect The Shut-Off Valve

    Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. 3 Switch box cover 4 Top cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 21: To Connect The Domestic Hot Water Pump

    2 Connect the alarm output cable to the appropriate terminals as 2 Connect the domestic hot water pump cable to the appropriate shown in the illustration below. terminals as shown in the illustration below. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 22: To Connect The Space Cooling/Heating On/Off Output

    4 Top cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 23: To Connect The Power Consumption Digital Inputs

    (normally closed contact) Wires: 2×0.75 mm² Maximum length: 50 m Safety thermostat contact: 16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 24: To Connect A Smart Grid

    ▪ There is a minimum distance of 2 m between the safety thermostat and the 3‑way valve. NOTICE Error. If you remove the jumper (open circuit) but do NOT connect the safety thermostat, stop error 8H-03 will occur. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 25 Jumper (factory-mounted). If you also connect a safety thermostat (Q4L), replace the jumper with the safety thermostat wires. Smart Grid pulse meter 1 Install the switch box metal insert. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 26: To Connect The Wlan Cartridge (Delivered As Accessory)

    X 5M X 5M.9 5 Connect the high voltage wiring as follows: 6.3.15 To connect the solar input Wires: 0.5 mm² Solar input contact: 5 V DC (voltage supplied by PCB) Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 27: To Connect The Dhw Output

    ▪ First time – Configuration wizard. When you turn ON the user interface for the first time (via the unit), the configuration wizard starts to help you configure the system. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 28: To Access The Most Used Commands

    The Advanced user pin code is 1234. Additional menu items for the screen and request to restart the system. user are now visible. When confirmed, the system will restart and recent changes will be applied. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 29: Configuration Wizard

    To manually recover it via the user interface, go to the zone: Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not. a Main LWT zone ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 30: Configuration Wizard: Backup Heater

    If the storage temperature setpoint is higher than 50°C and [E-0D] Glycol Filled system: Is the system no auxiliary boiler is installed, Daikin recommends NOT to filled with glycol? disable the backup heater second step because it will have ▪ 0: No a big impact on the required time for the unit to heat up the storage tank.
  • Page 31: Configuration Wizard: Main Zone

    Influence of the LWT setpoint mode [2.4] is as follows: ▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving water temperatures, either preset or custom. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 32: Configuration Wizard: Additional Zone

    ▪ 2-points curve ▪ Slope-offset curve Which type of curve you use to make adjustments, depends on your personal preference. "7.3.4  Using weather-dependent curves" [ 4  34]. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 33: 2-Points Curve

    ▪ Change the slope to differently increase or decrease the temperature leaving water different ambient ▪ : Storage tank temperatures. For example, if leaving water temperature is in ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 34: Using Weather-Dependent Curves

    ON/OFF setpoints for that zone or for the tank. When the maximum condition. or minimum setpoint is reached, the curve flattens out. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 35: Additional Zone

    ▪ 2: 2 contacts 7.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 36: Menu Structure: Overview Installer Settings

    Main zone pump fixed PWM Mixing valve turning time Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 37: Commissioning

    Next commissioning instructions in this chapter, a general ▪ Between the local supply panel and the indoor unit commissioning checklist is also available on the Daikin ▪ Between the indoor unit and the valves (if applicable) Business Portal (authentication required).
  • Page 38: To Perform An Air Purge

    Purpose Perform an actuator test run to confirm the operation of the different actuators. For example, when you select Pump, a test run of the pump will start. Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 39: To Set Up Bivalent Heat Sources

    ▪ Explain the user how to properly operate the system and what to do in case of problems. ▪ Show the user what to do for the maintenance of the unit. ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 40: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 41: Wiring Diagram: Indoor Unit

    (1) Main power connection (1) Main power connection SWB1 Main switch box Outdoor unit Outdoor unit SWB2 Backup heater switch box SWB1 Switch box (2) User interface (2) User interface ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 42 Smart Grid contacts Smartgrid feed-in Smart Grid feed-in Solar input Solar input Space C/H On/OFF output Space cooling/heating On/OFF output SWB1 Switch box (4) Option PCBs (4) Option PCBs Installation manual ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 43 A14P: P1-P2 user interface Power limitation A8P: X801M: 4-5 user interface communication demand input 4 signal 2 core 2x0.75 Only for LAN adapter A13P: P1-P2 user interface communication 4D132247 B ETSH/X(B)16P30+50EF Installation manual Daikin Altherma 3 H HT ECH₂O 4P679468-1A – 2022.07...
  • Page 44 4P679468-1 A 0000000A 4P679468-1A 2022.07 Verantwortung für Energie und Umwelt...