5

Connection

5.1

Installing the Base

The detector bases are screwed to the even, dry surface using two screws approx. 55 mm
apart.
To feed cables through for surface mounting, punch out the prepared entry points (X) on the
housing.
For flush-mounted cable insertion, feed the cable through the opening in the middle of the
base.
The long holes marked in the sketch with "Y" are intended for base installation in a flush
mount back box and should only be used for this purpose.
Notice!
i
Cables can be fed in and out on the same side.
On the FAA-420-SEAL and MSC 420, punch out the integrated seal with a sharp tool. Do not
cut with a knife.
5.2
Connection
Notice!
i
Keep shield wire as short as possible and insulate.