Bosch AVENAR detector 4000 User Manual page 17

Hide thumbs Also See for AVENAR detector 4000:
Table of Contents

Advertisement

AVENAR detector 4000
Installation location
Warehouse without
combustion-engine traffic
Conference room/waiting
room/exhibition hall
Kitchen/casino/restaurant
Warehouse with
combustion-engine traffic
Thermal sensor: fixed and
rate-of-rise temperature
Optical sensor
Thermal sensor: fixed
temperature
Optical and CO sensor
School/kindergarten
Theater/concert hall
Optical + thermal + CO
sensor: high sensitivity**
Optical + thermal + CO
sensor: low sensitivity**
Thermal and CO sensor***
CO sensor***
O = optical sensor, T
max
* If optical sensor sensitivity is low, the detector will only trigger if smoke as well as an increase in CO
concentration or temperature is detected.
** Suppression of single fire phenomena, only available for FAP-425-DOTCO-R
*** only available for FAP-425-DOTCO-R
Bosch Sicherheitssysteme GmbH
Detector type Sensitivity
Temperature
(T)
O, T
, T
, C Low (BR)
max
diff
O, T
, T
, C High (A2R)
max
diff
O, T
, C
Low (BS)
max
O, T
, T
, C Low (BR)
max
diff
T
, T
High (A2R)
max
diff
O
-
T
High (A2S)
max
O, C
-
O, T
, T
, C High (A2R)
max
diff
O, T
, T
, C High (A2R)
max
diff
O, T
, T
, C High
max
diff
O, T
, T
, C Low
max
diff
T
, T
, C
Low
max
diff
C
-
= thermal maximum unit, T
Optical (O)
High
Low*
Low*
Low*
-
Low
-
Low
Medium
Medium
High
Medium
-
-
= thermal differential unit, C = chemical sensor
diff
User manual
Programming | en
Standard
Chemical (C)
High
EN 54-5, EN 54-7,
EN 54-29
Medium
EN 54-5, EN 54-7
Low
EN 54-5, EN 54-7
Low
EN 54-5, EN 54-7
-
EN 54-5
-
-
-
EN 54-5
High
-
High
EN 54-5, EN 54-7,
EN 54-29
High
EN 54-5, EN 54-7,
EN 54-29
High
VdS 6019
High
VdS 6019
High
VdS 6018
High
VdS 6017
2023-06 | 07 | F.01U.283.550