Compatibility; Accessories; Detector Bases - Bosch AVENAR detector 4000 User Manual

Hide thumbs Also See for AVENAR detector 4000:
Table of Contents

Advertisement

AVENAR detector 4000
2.5

Compatibility

Notice!
i
The dual-optical detectors of the AVENAR detector 4000 series cannot be used with the
FPA-5000 type A panel controller.
Notice!
i
FAP-425-DOTCO-R is supported on AVENAR panel 8000 and AVENAR panel 2000 only.
2.6

Accessories

2.6.1

Detector bases

Detectors in the AVENAR detector 4000 series are operated in one of the following detector
bases.
The detector bases are suitable for surface mounting or for flush mounting. There are separate
fixing points for ceiling-mount boxes and for flush-mount boxes. They also fit all common bore
patterns.
The bases are made from white ABS plastic (color similar to RAL 9010) and have a matte
surface finish.
Bosch Sicherheitssysteme GmbH
Individual detector identification on the fire panel in the event of an alarm. Alarm
indication on the detector with a flashing red LED.
Programmable sensitivity, i.e. can be adjusted to the area of operation.
Increased detection and false alarm security thanks to evaluation of the temporal
behavior of fire and of disturbance variables.
Activation of a remote indicator is possible.
To prevent that unauthorized persons have access to the device, the locking clip can be
activated.
Dust-resistant labyrinth and cap construction.
The chamber maid plug (a cleaning opening with a plug) is for blowing out the optical
chamber with compressed air. (Not required for the FAH-425-T-R Heat detector.)
Use of shielded or unshielded cables permitted.
The LSN improved version line technology supports the connection of up to 254 AVENAR
detector 4000 series detectors per loop or stub (please observe national regulations in
this regard).
Flexible network structures without additional elements are possible (T-tapping is not
feasible with detector versions without rotaries).
Automatic or manual detector addressing selectable.
Status information and extensive diagnostic data (e.g. serial number, operating hours,
contamination level, EMC strengh, current analog values) is available on fire panel screen
and via Condition Monitoring.
Compliant with EN 54, EN 50131 and VdS guidelines.
For connecting to fire panels with extended range of LSN features.
In classic mode, it can be connected to BZ 500 LSN, UEZ 2000 LSN and UGM 2020 LSN
and to other panels or their receiver modules with identical connection properties but
with the existing LSN system limits.
User manual
System Overview | en
2023-06 | 07 | F.01U.283.550
9