4.2 Control Wiring
Class 2 low voltage control wiring should not be run in conduit with main power wiring and must be
separated from power wiring, unless class 1 wire of proper voltage rating is used.
Low voltage control wiring should be color-coded 18 AWG. For lengths longer than 100 ft, 16 AWG
wire shall be used.
Refer to wiring diagrams attached to indoor and outdoor sections to be connected.
Make sure separation of control wiring and power wiring has been maintained.