8.4
Selecting the reignition fre-
quency
When the boiler functions in normal on/off
heating mode, the minimum time between
two ignitions is set at three minutes (re-igni-
tion frequency).
This time can be changed by a minimum
of zero to a maximum of eight and a half
minutes.
• Enter the "programming mode" by se-
quentially pressing keys 12 - 13 - 14 (Fig.
8.22) for 10 seconds at the same time un-
til the letters Pr that alternate with code
01 are displayed on the LCD display, indi-
cating that "parameter 01" (Fig. 8.23) has
been activated.
12
Fig. 8.22
Fig. 8.23
• Scroll the various parameters using keys
13 or 14 until the letters Pr that alternate
with code 10 are displayed on the LCD
- 62 -
ADVANCED COMMISSIONING
14
13
display, indicating that "parameter 10"
(Fig. 8.24) has been activated.
Fig. 8.24
• Press keys 12 and 14 (Fig. 8.22) at the
same time until the value of parameter
10 (30=180 seconds) is displayed on the
LCD display (Fig. 8.25).
Fig. 8.25
• It is possible to modify parameter 10 by
00=0s to 99=600s using keys 13 or 14
(each increase or reduction by a unit on
the display corresponds to 6 seconds).
• By pressing key 12 (Fig. 8.22) confirma-
tion of the inserted value is obtained.
• Press keys 12 and 13 (Fig. 8.22) at the
same time to exit without changing the
value (return to the parameters list Fig.
8.24).
• Press sequentially keys, 12 - 13 and then
14 (Fig. 8.22) and hold in for 10 seconds
to exit the "programming mode".
Programming using the REMOTE control
Act on the programming of the REMOTE
control to select a minimum time between