Fitting the Devices
3.3 Surface-Mounted Devices with Detached On-Site Operation Panel
Plug the connecting cable into the on-site operation panel of the basic module.
²
Guide the connecting cable through the cut-out in the assembly wall.
²
Place the 2 contact washers on the top fastening holes.
²
Bolt down the on-site operation panels connected to one another on the assembly wall.
²
Check for secure attachment of the on-site operation panels on the assembly wall.
²

Activating the Battery

3.3.2
Removing the Protective Film
NOTE
i
i
The battery is covered with a protective film to protect it from mechanical damage and against premature
discharge.
The battery need not be removed from the battery compartment for activation.
Pull out the battery compartment.
²
Remove the protective film from the battery by simply pulling on the film tab.
²
Push the battery compartment back in again.
²

Grounding and Connecting Devices

3.3.3
Grounding Devices
!
DANGER
Danger due to device being improperly grounded
Incomplete and careless grounding leads to death, severe injury, and considerable material damage!
The device must be situated in the operating area for at least 2 hours before you connect it to the
²
power supply for the first time. This method prevents condensation of water in the device.
If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2
²
days. This will cause the electrolytic capacitors to form on the printed circuit board assemblies again.
²
Ground each module with solid low-impedance system grounding (cross-section ≥ 2.5 mm
grounding area ≥ M4).
Connecting Devices
Connect all cables and leads. Use the connection diagrams in the Hardware and Device manuals.
²
Tighten the terminal screws to the prescribed torques.
²

Tightening Torques of Fastening Screws

3.3.4
Tightening Torques for Terminal Screws
Type of Line
Litz wire with ring-type lug
58
Current
Voltage Terminal with
Terminal
Spring-Loaded Terminals
2.7 Nm
No ring-type lug
2
(≥ 0.1 in
Voltage Terminal with
Screw Connection
No ring-type lug
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018