Test And Diagnostics; Establishing Test Mode - Siemens SIPROTEC 5 V7.80 Operation

Table of Contents

Advertisement

Maintenance, On-the-Spot Assistance and Test

10.5 Test and Diagnostics

10.5
Test and Diagnostics

Establishing Test Mode

10.5.1
Safety Instructions
!
DANGER
Danger due to the execution of test functions
Noncompliance with safety instructions will result in death, serious physical injury, or considerable
material damage.
The execution of test functions requires a high degree of qualification and precise know-how of
²
system conditions.
Procedure
DIGSI 5 offers the possibility to start different test and diagnostic functions for a SIPROTEC 5 device in the
Online operating mode. In chapter
the device and DIGSI 5 offer you.
Activate the test functions via the menu bar and via different functions that you reach via the list view of the
device.
Open the device in the Online operating mode.
²
Open Test suite in the project tree.
²
[sctstsut-140211-01.tif, 1, en_US]
Figure 10-21
All subordinate test options appear in the data window. Select the desired test editor and start the test. If
configured, enter the confirmation ID. In some test functions the device switches to an operating mode that
first requires a system start of the device. Confirm this with DIGSI 5. The selected test function then becomes
available.
234
9.2.1 Test Functions
Test Suite
you will find the description of the test functions that
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018