Operation in the Operating State
8.6 Edit Measured and Metered Values
Enter the desired value in the Current value column. The input value is converted to the data format
²
according to IEC 61850. Because of the associated quantization, the resulting display value can differ
from the input. In addition, the input value is rounded to 6 digits. The display is limited to 6 digits. There-
fore please note that, in case of small pulse weighting, minor changes to large metered values can not be
reflected in the display.
To transfer the value to the device, click the Set button.
²
[scnrgwer-080413-01.tif, 1, en_US]
Figure 8-36

Setting and Resetting User-Defined Metered Values

8.6.4
Setting and resetting metered values on the device:
To set and reset, open the Measured values menu on the device.
²
Switch to the corresponding function group (for example, Line) in the User-defined values menu in
²
which the metered values have been arranged.
Select the metered value.
²
Reset the metered values if needed. Use the context-sensitive Reset key on the on-site operation panel.
²
If you select one level lower, you are brought to the metered values.
²
You can set the metered value to the desired value via the context-sensitive Change key. The input value
²
is converted to the data format according to IEC 61850. Because of the associated quantization, the
resulting display value can differ from the input. In addition, the input value is rounded to 6 digits. The
display is limited to 6 digits. Therefore please note that, in case of small pulse weighting, minor changes
to large metered values can not be reflected in the display.
Set the new value and activate acceptance with Enter.
²
Setting and resetting metered values with DIGSI 5:
Start the online mode with DIGSI 5.
²
Click (in the project tree bottom left) the Measured values menu item.
²
Double-click the function group (for example, Line) and the measured-value window appears in the oper-
²
ating range.
If you open the User-def. values tab in the measured-values window, the corresponding values can be
²
viewed.
If you click the Reset button, you can reset the current meter readings to 0.
²
Alternatively, you can set the meter to a value.
158
Overview of Energy Values
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-9, Edition 06.2018