X2 Profinet - Siemens SINUMERIK ONE NCU 1750 Equipment Manual

Hide thumbs Also See for SINUMERIK ONE NCU 1750:
Table of Contents

Advertisement

Wiring the screw-type terminal block
The required 24 VDC load power supply is wired to the screw-type terminal block (X1).
Danger of death caused by unsafe power supply
The 24 V direct voltage is to be configured as an extra-low voltage with protective separation
- DVC A or PELV according to EN 61800-5-1.
Power cables
Table 12-36
Characteristics
Connection option
Current carrying capacity
Max. cable length
Use flexible cables with a cross-section of 0.25 to 2.5 mm
power supply according to the maximum current that flows.
If you only use one wire per connection, an end sleeve is not required.
You can use end sleeves without an insulating collar according to DIN 46228/1.
12.3.4.3

X2 PROFINET

Data Transmission Rate and Cables
For PROFINET, you require a data transmission rate of 100 Mbit/s (Fast Ethernet). The interfaces
are designed for full-duplex mode; in other words, the ports can both transmit and receive. For
data transfer purposes you can use electrical twisted copper cables (twisted pair, 4-wire,
100Base-T):
• The transmission characteristics of these cables must meet the requirements of CAT5.
• The maximum length of the connections between the end device and network component
or between two network components (e.g. switch ports) must not exceed 100 m.
Pin assignment
Table 12-37
Pin
1
2
3
4
5
NCU 1750
Equipment Manual, 01/2022, A5E45627807B AE
DANGER
Cable specification at X1
PROFINET interfaces X2, ports 1, 2
Signal name
Signal type
TX+
O
TX-
O
RX+
I
N.C.
-
N.C.
-
Version
Up to 2.5 mm
2
max. 10 A
10 m
(or AWG 23 to AWG 13) for wiring the
2
Meaning
Transmit data +
Transmit data -
Receive data +
Reserved, do not use
Reserved, do not use
Connectable components
12.3 PP 72/48D PN 2/2A PN
137

Advertisement

Table of Contents
loading

Table of Contents