Connection - Siemens SINUMERIK ONE NCU 1750 Equipment Manual

Hide thumbs Also See for SINUMERIK ONE NCU 1750:
Table of Contents

Advertisement

Connectable components
12.1 NX10.3/NX15.3
12.1.4

Connection

Power supply X124
Table 12-2
Note
The two "+" and "M" terminals are jumpered in the connector and not in the device. This ensures
that the supply voltage is looped through.
The current consumption increases by the current consumption of DRIVE-CLiQ and the digital
outputs.
When using external power supplies (e.g. SITOP), the ground potential of the power supply must
be connected with the protective ground connection of the system (PELV).
Table 12-3
Characteristics
Connector type
Connectable cable types and conductor cross-sections
Stripped length
Tool
Tightening torque
Max. current carrying capacity, incl. loop-through
Max. cable length
106
Pin assignment for X124
Pin
+/-
+/-
M
M
Cable specification for X124
Rigid
Flexible
Flexible, with end sleeve without plastic sleeve
Flexible, with end sleeve with plastic sleeve
AWG / kcmil
Function
24 VDC power supply (20.4 V - 28.8 V)
Ground
Version
4-pin screw-type terminal
0.2 mm² to 2.5 mm²
0.2 mm² to 2.5 mm²
0.2 mm² to 2.5 mm²
0.2 mm² to 1.5 mm²
16 to 14
6-7 mm
Screwdriver 0.5 x 3 mm (M2.5)
0.4 to 0.5 Nm
20 A (15 A according to UL/CSA)
10 m
Equipment Manual, 01/2022, A5E45627807B AE
NCU 1750

Advertisement

Table of Contents
loading