Chapter 9
Digital Routing and Clock Generation

Using RTSI as Outputs

RTSI <0..7> are bidirectional terminals. As an output, you can drive any of the following signals
to any RTSI terminal:
AI Start Trigger (ai/StartTrigger)
AI Reference Trigger (ai/ReferenceTrigger)
AI Convert Clock
AI Sample Clock (ai/SampleClock)
AI Pause Trigger (ai/PauseTrigger)
AO Sample Clock
AO Start Trigger (ao/StartTrigger)
AO Pause Trigger (ao/PauseTrigger)
DI Start Trigger (di/StartTrigger)
DI Sample Clock (di/SampleClock)
DI Pause Trigger (di/PauseTrigger)
DI Reference Trigger (di/ReferenceTrigger)
DO Start Trigger (do/StartTrigger)
DO Sample Clock
DO Pause Trigger (do/PauseTrigger)
10 MHz Reference Clock
Counter n Source, Gate, Z, Internal Output
Change Detection Event
Analog Comparison Event
FREQ OUT
PFI <0..5>
Note
Signals with a

Using RTSI Terminals as Timing Input Signals

You can use RTSI terminals to route external timing signals to many different X Series
functions. Each RTSI terminal can be routed to any of the following signals:
AI Convert Clock (ai/ConvertClock)
AI Sample Clock (ai/SampleClock)
AI Start Trigger (ai/StartTrigger)
AI Reference Trigger (ai/ReferenceTrigger)
AI Pause Trigger (ai/PauseTrigger)
AI Sample Clock Timebase (ai/SampleClockTimebase)
9-6 | ni.com
*
(ai/ConvertClock)
*
(ao/SampleClock)
*
(do/SampleClock)
*
are inverted before being driven on the RTSI terminals.