Group 1 Fault Codes - Worcester Greenstar Ri Compact ErP Installation, Commissioning And Servicing Instructions

Wall hung rsf gas fired condensing regular boiler
Table of Contents

Advertisement

8.1.1

Group 1 fault codes

Flash
sequence
Type of fault
Light OFF
Light ON
Group 1
Flashing codes
1
Locking
2
Locking
3
Locking
4
Locking
5
Locking
1
5 seconds off
2
5 seconds off
3
5 seconds off
4
5 seconds off
5
5 seconds off
Fig. 100 Group 1 flash sequences
Greenstar Ri Compact
ErP
6720813282 (2015/07)
Fault
No fault
No ionisation detection after ignition
Loss of ionisation signal during operation
Gas valve error
First safety timing error/ignition timing error
Ionisation detected after burner stopped
Gas valve EV2 leak test failed
Gas valve EV1 leak test failed
Ionisation current detected before burner-start
Gas valve error
Ionisation sensor shorted
Fault code group 1
5 seconds off
5 seconds off
5 seconds off
Possible solutions/check
No boiler demand - boiler is OK
Heating demand on boiler- boiler is OK
Failure of four ignition attempts, the boiler waits 30
seconds before another attempt is made.
Reset the boiler by turning the control knob anti-
clockwise to the reset position.
An established flame has been extinguished.
Reset the boiler by turning the control knob anti-
clockwise to the reset position.
Gas valve coil disconnected. Check gas valve.
Reset the boiler by turning the control knob anti-
clockwise to the reset position.
The flame was not established during the first four
seconds of the ignition period.
Reset the boiler by turning the control knob anti-
clockwise to the reset position.
Gas valve leaking.
False flame detected.
Reset the boiler by turning the control knob anti-
clockwise to the reset position.
1 to 5 flashes
5 seconds off
5 seconds off
Fault finding and diagnosis
6720646610-66.2Wo
53

Advertisement

Table of Contents
loading

Table of Contents