Worcester Greenstar Ri Compact ErP Installation, Commissioning And Servicing Instructions page 46

Wall hung rsf gas fired condensing regular boiler
Table of Contents

Advertisement

Service and spares
Fig. 81 Moulded style seal
Fitting the "tubular" sump seal
3. Fit the Flueway sump seal [2] into the Flueway.
Ensure the seal is fitted fully into the recess in the underside of the
Flueway.
Before fitting the Flueaway:
▶ Ensure that the seal is clean and free of debris.
5.
Fig. 82 Tubular style sump seal
Combustion air inlet and gas pipe disconnection
1. Rotate the combustion air inlet pipe anti-clockwise to release from
the fan assembly and pull away from the fan.
2. Undo the top gas pipe connector at the gas valve.
2.
Fig. 83 Combustion air inlet pipe removal
46
1.
2.
6720803800-13.1Wo
1.
Fan removal
3. Rotate the exhaust pipe anti-clockwise to gain access to the fan
assembly securing screws.
4. Support the weight of the fan and remove the two screw securing the
fan.
3.
Fig. 84 Fan removal 1
5. Rotate the exhaust pipe clockwise.
6. Pull the fan assembly away from the mount, lift and rotate the fan
towards you. Ensure that the front of the fan clears the left hand front
castellated nut securing the burner housing.
7. Pull the gas pipe off the fan body connection, the pipe is secured by
the interference fit between the pipe and connector.
8. Remove the electrical connector and earth from the fan.
6.
Fig. 85 Fan removal 2
Greenstar Ri Compact
4.
5.
7.
ErP
6720813282 (2015/07)