Mounting of FH-L Series
• Make sure to tighten all installation screws securely.
• For good ventilation, provide a clearance of 50 mm or more above the sensor controller away from
other devices in the normal floor mounting. For the right and left sides, provide a clearance of 30 mm
or more, and for the back side, 15 mm or more. These clearances are also required when mounting
multiple sensor controllers side by side. For the back mounting, the back-side clearance of 15 mm is
nor required.
• Do not install the product immediately above significant heat sources, such as heaters, transformers,
or large-capacity resistors.
• Do not install the product in a cabinet containing high-voltage equipment.
• Do not install the Sensor Controller within 200 mm of power cables.
 Mounting the base of the Sensor Controller (Floor mounting)
Clearance: 30 mm
22
• Recommended tightening torque: 0.54 N
• The tolerance:
Vision System FH/FZ5 series Hardware Setup Manual (Z366)
Clearance: 50 mm
Clearance: 15 mm
Clearance: 30 mm
Four, M4 depth 6.5
100
±
0.2 mm
m to 0.6 N
m
5 Setup and Wiring