Troubleshooting - Theben thePrema S360-101 E UP WH Quick Start Manual

Presence detector
Table of Contents

Advertisement

Connection type
Max. cable cross-section
Size of flush-mounted box
Protection rating
Ambient temperature
CE Declaration of Conformity
Product overview
Type of
Channel Operating
installation
voltage
Ceiling
Light |
230 V AC
installation
HVAC
Ceiling
Light |
230 V AC
installation
HVAC
Ceiling
Light |
230 V AC
installation
HVAC

Troubleshooting

Fault
Cause
Light does not switch
Lux value is set too low; detector set on semi-au-
on and/or off if pre-
tomatic; light was switched off manually via push
sence is detected and
button or theSenda S; person not within detection
in darkness
area; obstruction(s) interrupting detection; time
delay set too short
Light stays on with
Lux value is set too high; light was briefly switched
detection of presence
on manually via push button or with theSenda S
despite sufficient
(wait 30 min.); detector is in test mode
brightness
Light does not switch
Wait for time delay (self-learning);
off and/or light swit-
thermal sources of interference in the detection
ches on spontaneously
area: fan heaters, incandescent lamps/halogen
when no one is present
spotlights, moving objects (e.g. curtains hanging in
an open windows);
Load (EBs, relays) not cleared
Push button does not
Device still in the start-up phase; illuminated push
function
button was used without neutral conductor;
Push button not led to the master
Light cannot be swit-
DIP switch to "corridor" position; push button
ched off with the push
not fed to the detector. Check wiring to the push
button
button
Device does not
Short circuit or several phases in parallel switching!
respond
Disconnect detector from the power supply for 5
mins. (thermal fuse)
Error flashing
Error in self-test;
(4 x per second)
Device not properly functional!
Guarantee
ThebenHTS presence detectors are manufactured with the
utmost care and using state-of-the-art technology and are
quality-tested. ThebenHTS AG therefore guarantees perfect
operation when used correctly. Should a fault occur, however,
ThebenHTS AG will fulfil the guarantee within the scope of the
general terms and conditions.
Screw terminals
max. 2 x 2.5 mm²
Size 1, Ø 55 mm (NIS, PMI)
IP 20 (IP 40 installed)
0 °C – 50 °C
This device conforms to the
safety regulations of the EMC
directive 2014/30/EU and of
NSR 2014/35/EU.
Colour
Type
Item
number
White
thePrema
S360 -101 E
Grey
thePrema
S360 -101 E
Special colour
thePrema
in accordance
S360 -101 E
with customer
information
Please note in particular:
that the guarantee period lasts 24 months from the date
of manufacture.
that the guarantee is invalidated if you, or a third party,
make changes or undertake repairs to the devices.
that, insofar as the presence detectors are connected
to a software-controlled system, the guarantee for this
connection is only valid when the indicated interface
specification is complied with.
We undertake to repair or replace as quickly as possible
all components of the delivered device that have become
defective or unusable through demonstrably poor material,
faulty construction or incomplete delivery up to the end of the
2070605
guarantee period.
2070606
Returns
2070608
In the event of a guarantee claim, please return the device to
the relevant dealer together with the delivery note and a brief
description of the fault.
Industrial property rights
The design as well as hardware and software of these devices
are protected by copyright.
Dimensions diagrams
Flush-mounting
Surface-mounted
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Theprema s360-101 e up gr20706052070606

Table of Contents