Installing The Direct Liquid Cooling Module - Dell PowerEdge R7625 Installation And Service Manual

Table of Contents

Advertisement

Figure 122. Installing the heat sink
Next steps
1. If removed,
install the air
2. Follow the procedure listed in the

Installing the Direct Liquid Cooling module

Prerequisites
Never uninstall the heat sink from a processor unless you intend to replace the processor or system board. The heat sink is
necessary to maintain proper thermal conditions.
1. Follow the safety guidelines listed in the
2. Follow the procedure listed in the
3. If installed,
remove the air
4. If installed, remove the processor dust cover.
5. For new heat sinks, refer to
NOTE:
Ensure anti-tilt wires on the DLC module are in the unlocked position.
NOTE:
The recommended maximum operating pressure is 15 psi (diverter opens at 15 psi).
Steps
1. Align the DLC module with the standoff screws on the system board.
NOTE:
Ensure that the DLC tubes and liquid cooling leak detection cable are placed towards the rear of the system.
154
Installing and removing system components
shroud.
After working inside your
Safety
instructions.
Before working inside your
shroud.
Installing the heat sink
system.
system.
step 1 and 2 for applying the thermal grease.