Removing The Adapter Perc Module - Dell PowerEdge R7625 Installation And Service Manual

Table of Contents

Advertisement

Figure 105. Installing the front mounting front PERC module
Next steps
1. Reconnect all the required cables.
2. If removed,
install the air
3.
Install the drive backplane
4. Follow the procedure listed in

Removing the adapter PERC module

Prerequisites
1. Follow the safety guidelines listed in the
2. Follow the procedure listed in the
3. If required,
remove the air shroud
4. If required,
remove the drive backplane
5.
Remove the cooling fan cage
6.
Remove the expansion card
7. Disconnect all the cables from the Adapter PERC card, observe the cable routing.
NOTE:
Refer
cable routing
NOTE:
Adapter PERC module must be installed only in expansion card riser 1 or riser 2.
Steps
1. Tilt the expansion card retention latch lock to open.
2. Pull the card holder before removing the card from the riser.
3. Hold the Adapter PERC module by the edges. and pull the module from the expansion card connector on the riser.
NOTE:
The numbers on the image do not depict the exact steps. The numbers are for representation of sequence.
138
Installing and removing system components
shroud.
cover.
After working inside your
Safety
instructions.
Before working inside your
or
remove the GPU air
cover.
assembly.
riser.
topic for more information.
system.
system.
shroud.